Failure Prevention and Malfunction Localization in Underground Medium Voltage Cables

Aizenberg, Igor and Belardi, Riccardo and Bindi, Marco and Grasso, Francesco and Manetti, Stefano and Luchetta, Antonio and Piccirilli, Maria Cristina (2020) Failure Prevention and Malfunction Localization in Underground Medium Voltage Cables. Energies, 14 (1). p. 85. ISSN 1996-1073

[thumbnail of energies-14-00085-v2.pdf] Text
energies-14-00085-v2.pdf - Published Version

Download (4MB)

Abstract

A smart monitoring system capable of detecting and classifying the health conditions of MV (Medium Voltage) underground cables is presented in this work. Using the analysis technique proposed here, it is possible to prevent the occurrence of catastrophic failures in medium voltage underground lines, for which it is generally difficult to realize maintenance operations and carry out punctual inspections. This prognostic method is based on Frequency Response Analysis (FRA) and can be used online during normal network operation, resulting in a minimally invasive tool. In order to obtain the good results shown in the simulation section, it is necessary to develop a lamped equivalent circuit of the network branch under consideration. The standard π-model is used in this paper to analyse sections of a medium voltage cable and the parameter variations with temperature are used to classify the state of health of the line. In fact, the variation of the electrical parameters produces a corresponding variation in the frequency response. The proposed system is based on the use of a complex neural network with feedforward architecture. It processes the frequency response, allowing the classification of the cable conditions with an accuracy higher than 90%.

Item Type: Article
Subjects: European Scholar > Energy
Depositing User: Managing Editor
Date Deposited: 05 Jan 2023 06:45
Last Modified: 31 May 2024 09:34
URI: http://article.publish4promo.com/id/eprint/612

Actions (login required)

View Item
View Item